- Lithium Battery Cabinet
Lithium battery cabinet Standardized cabinet, with perfect power supply and distribution, precision power measurement, flexible configuration and other features.
Battery cabinet Capacity:
DC512V50AH
DC512V100AH
DC512V200AH
-
Safe and reliable
The battery pack is equipped with a high-performance battery management system BMS, which has over discharge, over charge, over current, over temperature and low protection functions to ensure the safety of the battery pack.
-
Energy efficient
Lithium iron phosphate battery, high stability.
High energy density, saving space; Multiple groups can be used in parallel.
- Application scenario
- Government
- Finance
- Communication
- Education
- Traffic
- Weather
- Medical
- Radio and Television
- Business Tax
- Energy


- Technical specification
Model | LI-DC512050 DC512V50Ah | LI-DC512100 DC512V100Ah | LI-DC512200 DC512V200Ah |
Rated voltage | 512V | 512V | 512V |
Rated capacity | 50Ah | 100Ah | 200Ah |
Voltage range | 400V ~ 576V | 400V ~ 576V | 432.0 V ~ 576.0 V |
Cell specifications | 3.2 V / 50 ah | 3.2 V / 50 ah | 3.2 V / 100 ah |
Module specification | / | / | 16S 1P |
Number of series parallel | 1P160S | 160S 2P | 160S 2P |
Maximum discharge current | ≤ 200A | 400A | 200A |
Rated energy | 25.6 kWh | 51.2 kWh | 102.4 kWh |
Nominal power | 25.6 kW | 51.2 kW | 102.4 kW |
Maximum output power | 102.4 kW | 204.8 kW | 102.4 kW |
Maximum charging current (A) | / | / | 100A |
Discharge cut-off voltage (V) | / | / | 432.0 V |
Maximum charging voltage (V) | / | / | 584.0 V |
Cycle times (25℃,0.5C/1C,100%DOD) |
/ | / | > 2500 |
Backup time (≤ 4C) | ≥ 15min | ≥ 15min | ≥ 60min |
Single cluster battery pack, high pressure box configuration | 1 master +10 slave | 1 master +10 slave | 1 master +10 slave |
Single cell size: W * H * D (mm) | 440× 133× 470mm | 440× 133× 820mm | / |
Individual cabinet size | 600× 800× 2000mm | 600× 1000× 2000mm | / |
Module size: Width * Depth * Height (mm) | / | / | 440× 460× 133mm |
Cabinet dimensions: W x D x H (mm) | / | / | 600× 800× 2000mm |
Number of system clusters | 1 | 1 | 2 |
Total number of system cabinets | 1 | 1 | 2 |
Total system size: Width * Depth * height (mm) | 600× 800× 2000mm | 600× 1000× 2000mm | 1200× 800× 2000mm |
System reference weight | Approx. 455kg | 797kg | 1190.0 kg |
Operating temperature | Discharge -20℃ ~ 50℃, recommended 5℃ ~ 40℃ | Discharge -20℃ ~ 50℃, recommended 5℃ ~ 40℃ | Discharge -20℃ ~ 50℃, recommended 5℃ ~ 40℃ |
Operating temperature | Charging 0℃ ~ 45℃, recommended 15℃ ~ 30℃ | Charging 0℃ ~ 45℃, recommended 15℃ ~ 30℃ | Charging 0℃ ~ 45℃, recommended 15℃ ~ 30℃ |
Working humidity | / | / | < 95%R.H(Non-condensing) |
Altitude | Over 2500m, special instructions required | Over 2500m, special instructions required | Over 2500m, special instructions required |
Communication mode | RS485 / CAN2.0 | CAN2.0 / RS485 | CAN2.0 / RS485 |
Fire requirements | Perfluorohexanone /S aerosol (optional) | Perfluorohexanone /S aerosol (optional) | Perfluorohexanone /S aerosol (optional) |
Protection Class | IP20 | / | IP20 |