UPS-M3300 Series 20-60kVA Modular UPS

UPS-M3300 series 20-60kVA modular UPS adopts modular architecture to greatly improve availability; Easy-to-use and efficient design can effectively reduce engineering costs and operation and maintenance costs.

Power range: 20~60kVA

Working mode: three in three out/three in single out/single in single out, double conversion online

  • Safe and reliable

    Supports rack-mounted installation (a standard 19-inch cabinet with a depth of 1100mm or above is recommended) and tower-mounted installation.
    The design elements of the rack-mounted modular unit greatly meet the characteristics of flexibility, easy installation, space saving and easy maintenance required by today's small and medium-sized data centers.

  • Energy efficient

    ECO mode is supported.

  • Intelligent control

    The host is equipped with 7-inch LCD touch screen, color graphics display, easy operation, man-machine communication friendly.

Application scenario

  • Government

  • Finance

  • Communication

  • Education

  • Traffic

  • Weather

  • Medical

  • Radio and Television

  • Business Tax

  • Energy
Widely used in government, finance, communications, education, transportation, meteorology, radio and television, industrial and commercial taxation, medical health, energy and power and other industries.
    Technical specification
    Model UPS-M3300-20-10 UPS-M3300-40-10 UPS-M3300-60-10
    Capacity 20kVA 40kVA 60kVA
    Main input Input wiring 3-phase + N-wire +PE
    Input voltage 380/400/415VAC (line voltage); 220/230/240VAC (phase voltage)
    Input frequency 50/60Hz
    Power factor > 0.99
    Battery Battery voltage ± 192-± 264VDC (32 ~ 44 verses)
    Bypass Bypass voltage 380/400/415VAC (line voltage) 220/230/240VAC (phase voltage)
    Voltage range Default -20%-+15%; -40%-+25% optional
    Overload capacity 125%, long run; 130%, shut down after 10 minutes
    150%, shut down after 1 minute; 150%< Load, shutdown after 300 ms
    Output Rated output voltage 380/400/415VAC(line voltage); 220/230/240VAC(phase voltage)
    Rated frequency 50/60Hz
    Output Power factor 1
    Voltage accuracy 1.50%
    Inverter overload 102%, long-term operation; 110%, 1 hour later to the bypass
    125%, 10 minutes later to the bypass; 150%, 1 minute to bypass; > 150%, switch to bypass after 200 milliseconds
    Frequency accuracy 0.10%
    Tracking range Configurable, ± 0.5 Hz - & plusmn; 5Hz, default ± 3Hz
    System System efficiency Main mode ≥ 95%; Economic Model ≥ 98%; Battery Mode ≥ 94.5%
    Display LCD+LED+ Color touch screen 7 inches
    Language Multiple languages supported, Simplified Chinese, Traditional Chinese, English, Russian, Italian, Korean, Portuguese, Spanish, German, Polish, French, Turkish, Czech, Serbian
    Communication interface RS232, RS485, dry contact, SNMP card (optional), emergency shutdown
    Wiring mode Backward and down line optional Backward and down line optional Down line
    Working environment 0-40℃ (operating temperature); -25℃~70℃ (storage temperature); 0-95% (non-condensation)
    Cabinet type 2 Module machine 4 Module machine 6 Module machine
    Size: Width * Depth * Height (mm) Host 485× 697× 398 485× 697× 575 485× 751× 1033
    Host (Put in server cabinet) 485× 697× 308(7U) 485× 697× 485(11U) 485× 751× 928 (21U)
    Module 436× 590× 85mm (2U)
    Weight (kg) Host (including modules) 73 113 175
    Module 15.3 (UPS-MM10)