- CR8000-LC Series
Data center liquid cooling system overall solution product consists of the following modules:
· External cooling equipment and external piping
· Primary CDU and Primary Pipe network
· The CDU secondary side and the secondary side pipe network
· Cluster ring network
-
Based on data center N+1 redundancy design, high system reliability
-
Modular design concept, easy to site construction operations;
-
To engineering design, all modules factory prefabrication, quick operation on site;
-
Standardized packaging and construction process, high efficiency;
-
Can be based on data center planning to achieve up or down the pipe, the design layout is flexible;
-
Integrated solution, providing a complete set of solutions for data center liquid cooling;
- Technical specification
Name | Specifications |
Centralized management | Power Environment Monitoring and Server monitoring |
Display | 43 inch touch screen |
Maximum power supply | 2*2120kW (2* Double bus 800A) |
Intercolumn CDU cooling capacity | 4*350kW~1200kW(3+1) |
Inlet water temperature | 20℃~45℃ |
System cooling | Cold plate liquid cooling + backplane evaporative cooling (optional) |
Intercolumn Air conditioning | 6*65kW |
Cabinet dimensions: W x D x H (mm) | 600*1200/1400*2200 |
Cabinet bearing | > 3100kg |
Input voltage | AC380/DC240V |
Input routes | Two AC or one AC+ one DC |
Input AC voltage range | 180 Vac to 264 Vac |
Input frequency range | 45Hz to 65Hz |
Output rated voltage | AC220V |
Operating temperature | 5℃~40℃ |
Working humidity | 8% ~ 90% |
Working altitude | ≤ 3050m |